MULTI FUNCTION INSTALLATION TESTER
Complies with IEC 61557
- Complies with IEC 61557
- Designed to IP 54 Rating
- Live circuit and wiring connection check LED's
- Triple ranges insulation tests at 250, 500 and 1000V
- Triple range loop and PSC tests 15mA test current at 200Ω/2000Ω range(No RCD Trip)
- Phase angle selection on RCD ranges
- Polarity switch for continuity tests
- Auto-null facility for continuity tests
- Earth probe for loop impedance testing on extraneous metalwork
- Contact Voltage Reading
- Test of a large kind of RCD's: Standard, Selective, AC and A
(DC sensitive breakers)
Specification
| Continuity Testing | ||
|---|---|---|
| Measuring Ranges | 20/200/2000Ω (Auto-ranging) | |
| Open Circuit Voltage | >6V | |
| Short Circuit Current | >200mA DC | |
| Accuracy | ±(1.5%rdg+3dgt) | |
| Insulation Testing | ||
| Measuring Ranges | 20/200MΩ (Auto-ranging) | |
| Test Voltage | 250V 500V 1000V DC | |
| Output Voltage on Open Circuit | 250V+40 to 0% 500V+30 to 0% 1000V+20 to 0% |
|
| Rated Current | > 1mA | |
| Accuracy | ±(1.5%rdg+3dgt) | |
| Loop Impedance Testing | ||
| Rated Voltage | 230V AC +10 to 15% [50Hz] | |
| Voltage Measuring Range | 100 to 250V AC [50Hz] | |
| Impedance Ranges | 20/200/2000Ω | |
| Nominal Test Current | 25A (20Ω range) 15mA (200Ω range) 15mA (2000Ω range) | |
| Accuracy | 20Ω range ±(3%rdg +4dgt) 200Ω range ±(3%rdg +8dgt) 2000Ω range ±(3%rdg +4dgt) |
|
| PSC Testing | ||
| Rated Voltage | 230V AC +10 to 15% [50Hz] | |
| PSC Ranges | 200A (15mA Test Current) 2000A (25A Test Current) 20kA (25A Test Current) |
|
| Accuracy | PSC accuracy derived from measured loop impedance specification and measured voltage specification |
|
| RCD Testing | ||
| Rated Voltage | 230V AC +10 to 15% [50Hz] | |
| Trip Current Settings | RCD × 1/2 : 10,30,100,300,500,1000mA RCD × 1 : 10,30,100,300,500,1000mA RCD × 5 : 10,30,100,300mA (on × 5 ranges max current 1A) |
|
| Trip Current Duration | RCD × 1/2 × 1: 2000ms RCD fast: 50ms |
|
| Accuracy | Trip current +10 to 0% of test current at 230V Trip time ±(1%rdg + 3dgt) |
|
| Applicable standards | IEC 61010-1 CAT Ⅲ 300V Pollution Degree 2, IEC 61010-2-034, IEC 61557 | |
| Power source | R6/LR6 × 8 | |
| Dimension | 130(L) × 183(W) × 100(D)mm | |
| Weight | Approx. 1100g | |
| Accessories | KAPM10 (Test lead with IEC connecter)*1 7122B (Test leads) 7132A (External earth probe) 8923 (Fuse[0.5A/600V]) × 1 (included), 1 (spare) 9092(Cord case) 9121 (Shoulder Strap) R6(AA) × 8 Instruction Manual |
|
| Optional Accessories | 7133B (Distribution board test leads) | |
*1 KAMP10(EU):European SCHUKO plug
KAMP10(UK):British plug(13A)
KAMP10 (AU):Australian plug
KAMP10(SA):South African plug
Optional Accessories
Catalog & Document
-
- Product Catalog